VPFlowMate In-line
The VPFlowMate® combines state of the art silicon sensor technology with ease of use. Because of the high turndown ratio and low pressure drop, the VPFlowMate® is suitable for many applications. With a RS232 and 4..20 mA output, the VPFlowMate can be connected directly to a PC and most industrial equipment. The VPFlowMate in-line has removable in- and outlet piping for convenient installation and service.
Compressed air metering, energy monitoring, testing of pneumatic systems, quality inspection and testing, purge metering.
Product Description
Main Features
Specification
• Easy installation and use
• Direct display of actual flow and totalized flow
• Large measurement range, from leakage to normal consumption
• Solid state (CMOS) flow sensor
• Digital (RS232) output
• 4..20 mA Output
Delivery:
| Measurement specifications |
|
| Accuracy |
< 2% of full scale. A calibration report is issued with each flow
meter |
| Ranges |
See
range table below. Ranges specified at 20 deg C |
| Zero cutoff point |
Depends on model; typically 2% of full scale (1:50 range) |
| Temperature
range** |
0..50 oC |
| Pressure limit |
Designed to 16 bar maximum pressure*** |
| Humidity range |
Up to 95% Relative
Humidity. Non condensing |
| Gases |
Compressed air, non corrosive gases |
| Mechanical specifications |
|
| Connections |
See
table below |
| Dimensions |
See the technical drawings; The up- and downstream pipes are
integrated. Dimensions are at least
15*D upstream and 5*D
downstream. The maximum total length is limited to 1 meter for
convenient transport and handling. |
| Protection
type |
Designed to meet IP55. Not for outdoor use. |
| Wetted materials |
Epoxy, glass, stainless steel 316, anodised aluminium |
| Corrosion
resistance |
Avoid highly corrosive or acid environments |
| Electrical specifications |
|
| Outputs |
RS232, 4..20 mA,
pulse ; multi connector |
| Power supply |
12..24 Volt DC |
| Approvals/ conformity |
|
| CE |
EN 61326-1 |
| CE |
EN
50082-1 |
** NOTE: The temperature error is typically less than 0.2% of reading per degree Celsius. Optional
temperature calibration can be specified.
*** NOTE: The pressure error is typically 0.3% of full scale per bar deviation of the calibration pressure. The pressure error of the VPFlowMate® is specified for a range of +/- 3 bar around the
calibration pressure. Ask for custom calibration when using the VPFlowMate® at atmospheric or low line pressure.